An overview of the
This series single-phase epoxy resin casting insulation voltage transformer is fully enclosed products, suitable for rated frequency 50 hz or 60 hz, rated voltage 3 kv and 6 kv, 10 kv power system, power voltage measurement, monitoring and protection. This product conforms to the IEC186 and GB1207-1997 standard for voltage transformer
Types of meaning
Introduction of the structure
This series of voltage transformer is fully enclosed, epoxy resin core and winding note as a body, small volume, light weight, cover two pins with the outlet box, and there are three different direction of feed export
Technical parameters
1. Product standards: GB1207-1997 "voltage transformer"
2. The load power factor: COS Φ = 0.8 (lag)
3. The product surface creepage than meet the grade II pollution level
See table 4. Other technical parameters
Technical parameters
type | Rated voltage than V | Rated frequency | High accurate level and the corresponding rated output | Limit the output | The rated insulation level | note | |||
0.2 | 0.5 | 1 | 6P | ||||||
JDZ10-3A1 | 3000/100 | 50,60 | 15 | 30 | 60 | 150 | 3.6/25/40 | 同RZL10 | |
JDZ10-3A2 | |||||||||
JDZ10-6A1 | 6000/100 | 15 | 30 | 60 | 150 | 7.2/32/60 | |||
JDZ10-6A2 | |||||||||
JDZ10-10A1 | 10000/100 | 15 | 30 | 60 | 150 | 12/42/75 | |||
JDZ10-10A2 | |||||||||
JDZ10-3B1 | 3000/100 | 25 | 50 | 90 | 300 | 3.6/25/40 | |||
JDZ10-3B2 | 40 | 100 | 150 | 500 | |||||
JDZ10-6B1 | 6000/100 | 25 | 50 | 90 | 300 | 7.2/32/50 | |||
JDZ10-6B2 | 40 | 100 | 150 | 500 | |||||
JDZ10-10B1 | 10000/100 | 25 | 50 | 90 | 300 | 12/42/75 | |||
JDZ10-10B2 | 40 | 100 | 150 | 500 | |||||
DZ10-3AG | 3000/3/100/3/100/3 | 40 | 60 | 50 | 150 | 3.6/25/40 | |||
DZ10-6AG | 6000/3/100/3/100/3 | 40 | 60 | 50 | 150 | 7.2/32/60 | |||
DZ10-10AG | 10000/3/100/3/100/3 | 40 | 60 | 50 | 150 | 12/42/75 | |||
DZ10-3BG | 3000/3/100/3/100/3 | 50 | 90 | 50 | 400 | 3.6/25/40 | |||
DZ10-6BG | 6000/3/100/3/100/3 | 50 | 90 | 50 | 400 | 7.2/32/60 | |||
DZ10-10BG | 10000/3/100/3/100/3 | 50 | 90 | 50 | 400 | 12/42 |
KV rated insulation level